An orifice flow installation is calibrated for 0-250 m³/h at 0-25 kPa differential pressure, with constant fluid density. During commissioning, an applied differential pressure of 10.24 kPa produces 14.24 mA and a transmitter display of 160 m³/h, but the distributed control system (DCS) displays 200 m³/h. Both displays read correctly at zero and full scale. What explains the discrepancy?
Show answer & explanation
Correct answer: C - Square-root extraction is occurring twice; make the DCS input linear.